Interior spaces
SPACE-INT
pragmaticBIM.ch/space-int
Links the room programme, area verification, and discipline planning so that use, sizing, and technical requirements can be coordinated for each space.
Description
- Usable interior spaces modelled as continuous volumes.
- Room use is carried in LongName; Name may carry the room number.
Modelling guidelines
- Model as a volume with the space tool, storey by storey.
- From top of finished floor to underside of the structural ceiling - not a suspended ceiling. This allows other trades to reuse the space, for example to assign building services to it.
- No overlaps or duplicates.
- Fill every void in the building with a space object.
- For rental-area or energy-reference-area calculations, choose and agree one of three approaches in advance: create a separate disposable model used only for the evaluation, with the required space definitions; adjust the calculation using suitable factors; or knowingly accept the remaining inaccuracy.
Discussion point
- For discipline planning, defining the space volume from the top of the structural floor slab to the underside of the structural slab above would be beneficial. This would allow installations within the floor build-up to be assigned unambiguously to the space. However, many authoring tools do not support this approach reliably, so it is not generally recommended here.
FinishFloorHeightorFloorCoveringThicknesscould additionally document the level difference.
IFC entity
- IFC4
- IfcSpace
- IFC4.3
- IfcSpace
- IFC2x3
- IfcSpace
- Applicability rule
- (entity_ifc4=IfcSpace AND PredefinedType=SPACE AND Pset_SpaceCommon.IsExternal=FALSE) OR (entity_ifc2x3=IfcSpace AND InteriorOrExteriorSpace=INTERNAL AND Pset_SpaceCommon.IsExternal=FALSE)
Attributes
| Attribute | Definition | Used in |
|---|---|---|
| Name |
Unique technical room number for planning. It provides discipline designers with a stable ID for linking their data permanently to the space and identifying significant changes quickly. It should stay stable as long as:
Do not use for signage - signage room numbers change often and belong in SignageRoomNumber. |
+31 more
|
| PredefinedType |
Marks the object as a space. Allowed values
Note
|
+21 more
|
| InteriorOrExteriorSpace |
Marks the space as interior. Allowed values
Note
|
+21 more
|
| LongName |
Room use for interior spaces according to the brief. Allowed values
|
+32 more
|
| Reference Pset_SpaceCommon |
Area class of the space according to SIA 416 or SIA D0165. Allowed values
|
+1 more |
| IsExternal Pset_SpaceCommon |
Marks an interior space. Allowed values
|
|
| NetPlannedArea ePset_SpaceRequirement · m² |
Ordered target net area of the space. |
+2 more |
| MinClearHeight ePset_SpaceRequirement · m |
Required minimum clear height of the space. |
+2 more |
| MinClearLength ePset_SpaceRequirement · m |
Required minimum clear length of the space. |
+2 more |
| MinClearWidth ePset_SpaceRequirement · m |
Required minimum clear width of the space. |
+2 more |
| SignageRoomNumber ePset_Space |
Room number for wayfinding signage (labelling, orientation). Separate from the technical planning room number (Name), because signage numbers often change and are therefore not stable identifiers for planning and operation. |
|
| FloorCovering Pset_SpaceCoveringRequirements |
Interior floor covering type for early planning and operation - as a space property. From tendering on, the floor build-up is modelled as well. Allowed values
|
|
| TotalHeatLoss Pset_SpaceThermalDesign · W |
Heating load for each space at design conditions as the basis for sizing heat emission. Note
|
|
| DesignAreaLoad ePset_SpaceRequirement · kN/m² |
Agreed design area load for the usage agreement. |
|
| DesignPointLoad ePset_SpaceRequirement · kN |
Agreed design point load for the usage agreement. |
|
| VibrationRequirements ePset_SpaceRequirement |
Agreed vibration requirements for the usage agreement according to ISO vibration criteria and Vibration Criterion (VC) per IEST. Allowed values
|
|
| DesignAreaLoadActual ePset_Space · kN/m² |
Verified actual area load for comparison with the usage agreement. |
|
| DesignPointLoadActual ePset_Space · kN |
Verified actual point load for comparison with the usage agreement. |
|
| VibrationRequirementsActual ePset_Space |
Verified actual vibration class for comparison with the usage agreement according to ISO vibration criteria and Vibration Criterion (VC) per IEST. Allowed values
|
|
| WinterTemperatureMin ePset_SpaceRequirement · °C |
Agreed minimum room temperature in winter. |
|
| WinterTemperatureMax ePset_SpaceRequirement · °C |
Agreed maximum room temperature in winter. |
|
| SummerTemperatureMin ePset_SpaceRequirement · °C |
Agreed minimum room temperature in summer. |
|
| SummerTemperatureMax ePset_SpaceRequirement · °C |
Agreed maximum room temperature in summer. |
|
| RelativeHumidityMin ePset_SpaceRequirement · % |
Agreed minimum relative humidity in the space. |
|
| RelativeHumidityMax ePset_SpaceRequirement · % |
Agreed maximum relative humidity in the space. |
|
| OutdoorAirFlowRate ePset_SpaceRequirement · m³/h |
Agreed outdoor airflow rate for the space. |
|
| PeakOccupancy ePset_SpaceRequirement · Personen |
Agreed maximum number of people present at the same time. |
|
| DailyOperatingHours ePset_SpaceRequirement · h/Tag |
Agreed daily operating duration of the space. |
|
| RequiredIlluminance ePset_SpaceRequirement · lx |
Agreed average illuminance in the space. |
|
| WinterTemperatureMinActual ePset_Space · °C |
Verified actual minimum room temperature in winter. |
|
| WinterTemperatureMaxActual ePset_Space · °C |
Verified actual maximum room temperature in winter. |
|
| SummerTemperatureMinActual ePset_Space · °C |
Verified actual minimum room temperature in summer. |
|
| SummerTemperatureMaxActual ePset_Space · °C |
Verified actual maximum room temperature in summer. |
|
| RelativeHumidityMinActual ePset_Space · % |
Verified actual minimum relative humidity in the space. |
|
| RelativeHumidityMaxActual ePset_Space · % |
Verified actual maximum relative humidity in the space. |
|
| OutdoorAirFlowRateActual ePset_Space · m³/h |
Verified actual outdoor airflow rate for the space. |
|
| PeakOccupancyActual ePset_Space · Personen |
Verified actual maximum number of people present at the same time. |
|
| DailyOperatingHoursActual ePset_Space · h/Tag |
Verified actual daily operating duration of the space. |
|
| RequiredIlluminanceActual ePset_Space · lx |
Verified actual average illuminance in the space. |
|
| Checkliste ePset_Space |
Free-text description of fit-out work in the room including sequence - so contractors on site can see what needs to be done. |
|
| UsageUnitReference ePset_Space |
Stable reference of the usage unit to which the space belongs, for example an apartment, office unit, or commercial unit. It should where possible be populated using an algorithm based on the space's geometric position within the corresponding gross volume. Note
|
|
| FireCompartmentReference ePset_Space |
Stable reference of the fire compartment to which the space belongs according to the fire-protection concept. |
|
| SecurityZoneReference ePset_Space |
Stable reference of the security zone to which the space belongs according to the security concept. |
|
| SecurityLevel ePset_Space |
Security level of the space according to the security concept. Allowed values
|
|
| ProtectionGoal ePset_Space |
Protection goal of the space according to the security concept. Allowed values
|
|
| NetFloorArea Qto_SpaceBaseQuantities · m² |
Net floor area of the modelled space. |
|
| NetPerimeter Qto_SpaceBaseQuantities · m |
Net perimeter length at floor level of the modelled space - excluding segments at virtual boundaries and openings; may include the perimeter of fixed fittings such as columns. |
|
| NetVolume Qto_SpaceBaseQuantities · m³ |
Net volume of the modelled space. |
|
| Height Qto_SpaceBaseQuantities · m |
Height of the modelled space volume. |
+1 more |
| FinishCeilingHeight Qto_SpaceBaseQuantities · m |
Suspended ceiling height - clear height from top of finished floor to underside of the suspended ceiling. Note
|
|
| CeilingCovering Pset_SpaceCoveringRequirements |
Ceiling material for early planning - as a space property only, without a modelled suspended ceiling. Allowed values
|
|
| WallCovering Pset_SpaceCoveringRequirements |
Wall finish quality for space-based tendering - without a separately modelled wall covering. Allowed values
|
|
| GrossWallArea Qto_SpaceBaseQuantities · m² |
Gross area of the wall surfaces bounding the space before deducting openings. |
|
| NetWallArea Qto_SpaceBaseQuantities · m² |
Net area of the wall surfaces bounding the space after deducting modelled openings. |
|
| HandicapAccessible Pset_SpaceCommon |
Marks whether the space is accessible and included in the coloured accessible route. Allowed values
|
|
| NoiseLoad ePset_Space |
Noise load of the room as the source under SIA 181, derived from its use. Together with the noise sensitivity of the neighbouring room it sets the sound insulation requirement of walls, slabs and doors between the rooms. |
+1 more |
| NoiseSensitivity ePset_Space |
Noise sensitivity of the room as the receiver under SIA 181, derived from its use. Together with the noise load of the neighbouring room or the exterior noise it sets the sound insulation requirement of the surrounding elements. |
+1 more |
| EscapeRouteClearWidth ePset_Space · m |
Planned clear width of the horizontal escape route in the space, at its narrowest point; give it only for spaces on an escape route (e.g. corridor). |
Related elements
-
SPACE-EXT
Exterior spaces
Makes usable exterior areas measurable for area verification, use planning, and coordination between the building and its surroundings.
-
SPACE-ELEVATOR
Lift
Enables the occupied area to be assigned by storey so that area verification can be maintained correctly.
-
SPACE-AIR
Air spaces
Prevents non-occupiable volumes from being counted as floor area while providing a spatial reference for building services.