Use case Design

Derive SIA 181 sound insulation requirements from room use

DES-SOUND-SIA181 pragmaticBIM.ch/des-sound-sia181

Set the noise load and noise sensitivity of every room and derive the sound insulation requirement of every separating element from them, so missing or too low requirements between usage units show up before the tender.

Starting point

  • Sound insulation requirements are often set as a flat value per element type, although under SIA 181 they depend on the pair of rooms: on the noise in the source room and on the sensitivity of the receiving room.
  • Evaluating room pairs by hand misses individual separating elements, such as the wall between the stairwell and a bedroom or the apartment entrance door, and the gap only shows up in the acoustic verification or the acceptance measurement.

Goal & benefit

  • Every room carries its noise load and noise sensitivity; the requirement of each separating element follows by rule from the room pair and the agreed requirement level.
  • Separating elements between usage units without a requirement, and verified values below the requirement, are reported per element.

Process

  1. Provide the rooms with usage unit, noise load and noise sensitivity, and take the requirement level from the sound insulation project goal.
  2. Derive the airborne and impact sound requirements for walls, slabs and doors from the room pair, those for exterior elements from exterior noise and noise sensitivity, and assign them to the elements.
  3. Check the verified values against the requirements and resolve deviations with the acoustic consultant.

Deliverable

  • Architecture model with noise load and noise sensitivity per room and a sound insulation requirement per separating element, door and exterior element
  • Check report listing missing requirements and values not reached