Rule Fire protection directive 26-15 Hazardous substances

Tyre stores in buildings: on an exterior wall, EI 60 up to 60 t/600 m², above that EI 90 with sprinklers and foam

VKF-26-15-020 pragmaticBIM.ch/vkf-26-15-020

Stores are on an exterior wall and have clearing openings of at least 2 × 2 m leading directly outdoors. Up to 100 m² the store may stand in the usage unit without fire-resistant separation.

Description

Up to 60 t or 600 m² it is separated as a fire compartment EI 60 and has smoke and heat exhaust. Above that it is a fire compartment EI 90 with a smoke and heat exhaust concept for approval and a sprinkler system with film-forming foam agent. At most 240 t are stored per compartment at a compartment size of 2,400 m². Not yet checkable: the model does not show stored mass, storage area and storage type of tyres and derived products.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 13)

More rules for Fire protection directive 26-15 Hazardous substances