Rule Fire protection directive 26-15 Hazardous substances

Stores of pyrotechnic articles: cool and dry, locked, EI 30 doors opening in escape direction, extinguishing equipment at the entrance

VKF-26-15-023 pragmaticBIM.ch/vkf-26-15-023

Pyrotechnic articles stay in their shipping and packaging units. Storage rooms are cool, dry, well ventilated and kept at as constant a temperature as possible.

Description

Electrical equipment is fixed and built to the recognised rules for rooms at fire risk. Only persons working there have access, and the rooms are locked when left. Smoking and open fire are prohibited, with a clearly visible sign. Suitable extinguishing equipment is provided at the entrances. Doors to the building interior are EI 30 and open in the escape direction. Police and fire brigade know location and type of the stored goods. Large stores (over 300 kg gross) are not located in a residential zone and are protected against lightning. Not yet checkable: the model does not show category, gross mass, storage type and sales area of pyrotechnic articles.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 15)

More rules for Fire protection directive 26-15 Hazardous substances