Rule Fire protection directive 26-15 Hazardous substances

Petrol pumps outside buildings with 3 m distance or an EI 60 wall without openings

VKF-26-15-021 pragmaticBIM.ch/vkf-26-15-021

Petrol pumps stand outside buildings and installations and keep 3 m distance from them. The distance may be smaller if the building wall within 3 m on both sides and 1 m above the pump is EI 60 and without openings.

Description

Permanent, clearly visible no-smoking signs are fixed at the pumps, and suitable portable extinguishers are provided. Not yet checkable: the model does not show substance classification, stored quantity, type and location of hazardous substances.

Source

VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 13)