Rule Fire protection directive 26-15 Hazardous substances
High-bay racking with hazardous substances: extinguishing system, 18 m storage height, ventilation, aisles as fire compartments
VKF-26-15-022
pragmaticBIM.ch/vkf-26-15-022
High-bay racking is protected with automatic extinguishing systems.
Description
For liquids with a flash point up to 60 °C the storage height is at most 18 m; areas with highly flammable liquids are ventilated artificially, sized for a room height of 3 m, and such liquids are stored only if structural and fire-fighting additional measures reliably limit fire spread. Explosive substances, substances with special fire behaviour and gas cylinders with combustible or toxic gas are excluded. Battery charging stations and film shrink equipment are allowed only with fire compartment separation from the store. Storage aisles are fire compartments; several may be combined if floor area 600 m² and room volume 12,000 m³ are not exceeded. Not yet checkable: the model does not show substance classification, stored quantity, type and location of hazardous substances.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 13)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-023
Stores of pyrotechnic articles: cool and dry, locked, EI 30 doors opening in escape direction, extinguishing equipment at the entrance
Pyrotechnic articles stay in their shipping and packaging units. Storage rooms are cool, dry, well ventilated and kept at as constant a temperature as possible.
-
VKF-26-15-024
Pyrotechnic stores by quantity: up to 50 kg EI 30, up to 300 kg EI 60, up to 1,000 kg on an exterior wall, above that free-standing with 20 m distance
Up to 50 kg gross (temporary, at most 1 month) rooms are built EI 30 and, with low fire risk, may serve other purposes. Up to 300 kg gross, rooms EI 60 without other use are needed.
-
VKF-26-15-025
Night and short-term stores of pyrotechnic articles: RF1 containers with 5 or 10 m distance or an EI 60 screen wall
The day's stock from outdoor sales is kept outside opening hours in storage rooms under 11.2.1 to 11.2.5. Fireworks of categories 1 to 3 may be stored up to 1,000 kg gross in free-standing, dedicated RF1 containers.