Rule Fire protection directive 24-15 Heating plant
Boiler room in buildings with several compartments: EI 30 up to 70 kW, EI 60 above, doors EI 30
VKF-24-15-004
pragmaticBIM.ch/vkf-24-15-004
Firing units stand in separate boiler rooms. Their fire resistance depends on the total nominal heat output: up to 70 kW the use-related compartment value, at least EI 30; above that at least EI 60.
Description
Doors are EI 30 and, above 70 kW, open in the direction of escape. Up to 70 kW and with low fire risk the room may also serve other purposes. The same applies to non-electric heat pumps, stationary combustion engines and combined heat and power plants. Not yet checkable: the model does not show nominal heat output, fuel, type of installation and fire resistance of the boiler room.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 6)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-005
Boiler room with direct access from outdoors: above 1,200 kW on ground floor or lower, above 600 kW from 2nd basement
Boiler rooms on the ground floor or lower for plants above 1,200 kW nominal heat output, and boiler rooms on the second basement or lower for plants above 600 kW, get direct access from outdoors.
-
VKF-24-15-006
Open installation in single-storey halls and commercial buildings with low fire load
In single-storey halls and multi-storey industrial and commercial buildings with use-related compartments, firing units of any output may stand openly if operation requires it, the clearances are kept and the fire load in the room is low.
-
VKF-24-15-007
Ventilation and combustion air: supply from outdoors, openings not closable
Room-air-dependent firing units stand only in ventilated rooms, and combustion air must be supplied from outdoors. Combustion-air openings must not be closed unless a safety device allows operation only with the closure open.