Rule Fire protection directive 24-15 Heating plant
Ventilation and combustion air: supply from outdoors, openings not closable
VKF-24-15-007
pragmaticBIM.ch/vkf-24-15-007
Room-air-dependent firing units stand only in ventilated rooms, and combustion air must be supplied from outdoors. Combustion-air openings must not be closed unless a safety device allows operation only with the closure open.
Description
Systems that extract room air, such as kitchen extract or tumble dryers, must not impair safe operation. Room-air-independent units with an air-flue system need no air openings. Not yet checkable: the model does not show nominal heat output, fuel, type of installation and fire resistance of the boiler room.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 7)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-008
Accessibility, safety devices and shut-off devices of firing units
Units and flue system are easily accessible for operation, maintenance and cleaning at all times.
-
VKF-24-15-009
Base plate, floor protection and wall behind firing units in heat-resistant RF1
On combustible floor constructions firing units stand on a base plate of heat-resistant RF1, individually made units such as tiled stoves on a 0.12 m thick slab of stone, concrete or equivalent. In front of solid-fuel units lies a heat-resistant RF1 floor covering extending 0.4 m in front of the loading opening.
-
VKF-24-15-010
Clearances to combustibles: 0.1 / 0.2 / 0.4 m by surface temperature, 0.8 m and 2 m for radiation
Adequate clearances apply to all combustible materials, as given in the declaration of performance or VKF technical information, otherwise 0.1 m for surface temperatures up to 100 °C, 0.2 m up to 200 °C and 0.4 m up to 400 °C.