Rule Fire protection directive 24-15 Heating plant
Boiler room with direct access from outdoors: above 1,200 kW on ground floor or lower, above 600 kW from 2nd basement
VKF-24-15-005
pragmaticBIM.ch/vkf-24-15-005
Boiler rooms on the ground floor or lower for plants above 1,200 kW nominal heat output, and boiler rooms on the second basement or lower for plants above 600 kW, get direct access from outdoors.
Description
Not yet checkable: the model does not show nominal heat output, fuel, type of installation and fire resistance of the boiler room.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 6)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-006
Open installation in single-storey halls and commercial buildings with low fire load
In single-storey halls and multi-storey industrial and commercial buildings with use-related compartments, firing units of any output may stand openly if operation requires it, the clearances are kept and the fire load in the room is low.
-
VKF-24-15-007
Ventilation and combustion air: supply from outdoors, openings not closable
Room-air-dependent firing units stand only in ventilated rooms, and combustion air must be supplied from outdoors. Combustion-air openings must not be closed unless a safety device allows operation only with the closure open.
-
VKF-24-15-008
Accessibility, safety devices and shut-off devices of firing units
Units and flue system are easily accessible for operation, maintenance and cleaning at all times.