Rule Fire protection directive 24-15 Heating plant
Open installation in single-storey halls and commercial buildings with low fire load
VKF-24-15-006
pragmaticBIM.ch/vkf-24-15-006
In single-storey halls and multi-storey industrial and commercial buildings with use-related compartments, firing units of any output may stand openly if operation requires it, the clearances are kept and the fire load in the room is low.
Description
Not yet checkable: the model does not show nominal heat output, fuel, type of installation and fire resistance of the boiler room.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 7)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-007
Ventilation and combustion air: supply from outdoors, openings not closable
Room-air-dependent firing units stand only in ventilated rooms, and combustion air must be supplied from outdoors. Combustion-air openings must not be closed unless a safety device allows operation only with the closure open.
-
VKF-24-15-008
Accessibility, safety devices and shut-off devices of firing units
Units and flue system are easily accessible for operation, maintenance and cleaning at all times.
-
VKF-24-15-009
Base plate, floor protection and wall behind firing units in heat-resistant RF1
On combustible floor constructions firing units stand on a base plate of heat-resistant RF1, individually made units such as tiled stoves on a 0.12 m thick slab of stone, concrete or equivalent. In front of solid-fuel units lies a heat-resistant RF1 floor covering extending 0.4 m in front of the loading opening.