Rule Fire protection directive 14-15 Use of building materials
Evacuation rooms, airlocks and anterooms: assignment to escape routes
VKF-14-15-015
pragmaticBIM.ch/vkf-14-15-015
For materials, evacuation rooms count as vertical escape routes, except patient rooms and horizontal escape routes in accommodation. Airlocks count as vertical escape routes, anterooms as horizontal ones.
Description
Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 9)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-001
High-rise buildings: external wall and cladding system made of RF1 materials
The external wall and the external wall cladding system of high-rise buildings are made of RF1 materials. Exceptions are plastic anchors, point back-anchorages of insulation and components of negligible area such as joints or seals.
-
VKF-14-15-002
High-rise buildings: external wall with combustible layers encapsulated on all sides K 60
Where a high-rise external wall consists of single layers containing combustible materials, it counts as RF1 as a whole if it is encapsulated on all sides with K 60 - RF1. The gaps are filled without voids with RF1 materials.
-
VKF-14-15-003
External wall cladding systems: reaction to fire by building height and use
The required reaction-to-fire group of external wall cladding systems rises with building height. In low buildings, RF3 materials generally suffice for other uses, while for accommodation the insulation layer stays RF1.