Rule Fire protection directive 14-15 Use of building materials
High-rise buildings: external wall and cladding system made of RF1 materials
VKF-14-15-001
pragmaticBIM.ch/vkf-14-15-001
The external wall and the external wall cladding system of high-rise buildings are made of RF1 materials. Exceptions are plastic anchors, point back-anchorages of insulation and components of negligible area such as joints or seals.
Description
With an extinguishing-system concept, RF2 suffices for light bands. Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 5)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-002
High-rise buildings: external wall with combustible layers encapsulated on all sides K 60
Where a high-rise external wall consists of single layers containing combustible materials, it counts as RF1 as a whole if it is encapsulated on all sides with K 60 - RF1. The gaps are filled without voids with RF1 materials.
-
VKF-14-15-003
External wall cladding systems: reaction to fire by building height and use
The required reaction-to-fire group of external wall cladding systems rises with building height. In low buildings, RF3 materials generally suffice for other uses, while for accommodation the insulation layer stays RF1.
-
VKF-14-15-004
Medium height: subdivide combustible facade, fire spread at most two storeys
In medium-height buildings with combustible external wall cladding or thermal insulation, the facade is subdivided structurally so that a fire spreads at most two storeys above the storey of origin before the fire brigade attacks. The fire brigade must be able to reach the facade surfaces for firefighting.