Rule Fire protection directive 14-15 Use of building materials

External wall cladding systems: reaction to fire by building height and use

VKF-14-15-003 pragmaticBIM.ch/vkf-14-15-003

The required reaction-to-fire group of external wall cladding systems rises with building height. In low buildings, RF3 materials generally suffice for other uses, while for accommodation the insulation layer stays RF1.

Description

In medium-height buildings, other uses with a structural concept need RF2; RF3 is allowed in VKF-recognized or equivalent constructions. High-rise buildings require RF1. The table also distinguishes the classified system, the cladding, the insulation or intermediate layer and light bands, as well as structural and extinguishing-system concepts. Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.

Source

VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 7)