Rule Fire protection directive 14-15 Use of building materials
High-rise buildings: external wall with combustible layers encapsulated on all sides K 60
VKF-14-15-002
pragmaticBIM.ch/vkf-14-15-002
Where a high-rise external wall consists of single layers containing combustible materials, it counts as RF1 as a whole if it is encapsulated on all sides with K 60 - RF1. The gaps are filled without voids with RF1 materials.
Description
Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 5)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-003
External wall cladding systems: reaction to fire by building height and use
The required reaction-to-fire group of external wall cladding systems rises with building height. In low buildings, RF3 materials generally suffice for other uses, while for accommodation the insulation layer stays RF1.
-
VKF-14-15-004
Medium height: subdivide combustible facade, fire spread at most two storeys
In medium-height buildings with combustible external wall cladding or thermal insulation, the facade is subdivided structurally so that a fire spreads at most two storeys above the storey of origin before the fire brigade attacks. The fire brigade must be able to reach the facade surfaces for firefighting.
-
VKF-14-15-005
Rendered external insulation with combustible insulant: fire barrier at every storey
External thermal insulation composite systems with a combustible insulant on medium-height buildings are a VKF-recognized or equivalent construction, or have a circumferential fire barrier made of an RF1 material with a melting point of at least 1000 °C and at least 0.2 m high at every storey.