Rule Fire protection directive 14-15 Use of building materials
External fabrics and films: reaction to fire, distance and position
VKF-14-15-008
pragmaticBIM.ch/vkf-14-15-008
Fabrics and films fixed on the outside are made of at least RF2 materials, on facades with an RF1 outer layer at least RF3. Combustible fabrics and films are only possible in front of facade areas without openings and fixed glazing, and keep at least 0.9 m distance in width and height from openable windows.
Description
They start only from the first upper floor, or from the ground floor on low buildings. In front of and above escape routes special protective measures are needed, and smoke and heat exhaust systems must not be impaired. On high-rise buildings the fire authority sets the measures. Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 6)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-009
Materials with critical behaviour (cr) generally not usable indoors
Materials with critical behaviour (cr) are generally not usable inside buildings. Exceptions are cables, single-layer membrane facades and materials under a void-free covering with a minimum thickness of 0.5 mm (RF1), 3 mm (RF2) or 5 mm (RF3).
-
VKF-14-15-010
Vertical escape routes: reaction to fire of linings and structures
In vertical escape routes (stairwells) of low and medium-height buildings with a structural concept, walls and floors with fire resistance, wall and ceiling linings, classified systems, stretched ceilings and stair and landing structures are made of RF1 materials; floor coverings are at least RF2.
-
VKF-14-15-011
Horizontal escape routes: reaction to fire of linings
In horizontal escape routes of low and medium-height buildings, wall and ceiling linings and classified systems are made of RF1 materials with a structural concept and of RF2 with an extinguishing-system concept; stretched ceilings are RF1 or RF2, one group lower where more than 5 m above walkable areas.