Rule Fire protection directive 14-15 Use of building materials
Horizontal escape routes: reaction to fire of linings
VKF-14-15-011
pragmaticBIM.ch/vkf-14-15-011
In horizontal escape routes of low and medium-height buildings, wall and ceiling linings and classified systems are made of RF1 materials with a structural concept and of RF2 with an extinguishing-system concept; stretched ceilings are RF1 or RF2, one group lower where more than 5 m above walkable areas.
Description
Floor coverings are RF3. Fire-resistant walls, floors and columns in accommodation are made of RF1. Where there is no fire-rated closure between a horizontal and a vertical escape route, the requirements of vertical escape routes apply. High-rise buildings require RF1. Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 10)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-012
Escape routes: combustible area share at most 10 %
In escape routes, the area share of combustible materials such as luminous panels, pin boards, linings or balustrade infills is at most 10 % of the stairwell floor area per storey or of the floor area of the horizontal escape route. Partial areas are at most 2 m² and keep at least 2 m distance from each other.
-
VKF-14-15-013
Other interior rooms: minimum reaction-to-fire requirements
In interior rooms outside escape routes, RF3 materials generally suffice in low and medium-height buildings. Exceptions: in accommodation and rooms with large occupancy, stretched ceilings are RF1 with a structural concept and RF2 with an extinguishing-system concept.
-
VKF-14-15-014
Interior fit-out: thin coatings and linear substructures where RF1/RF2 is required
Where RF1 is required for interior walls, floors and ceilings, combustible coatings such as paint, wallpaper or veneer up to 1.5 mm thick are allowed on the room side. Where RF1 or RF2 is required, linear substructures such as battens may be RF3, provided the visible side has a closed layer of the required group.