Rule Fire protection directive 14-15 Use of building materials
Materials with critical behaviour (cr) generally not usable indoors
VKF-14-15-009
pragmaticBIM.ch/vkf-14-15-009
Materials with critical behaviour (cr) are generally not usable inside buildings. Exceptions are cables, single-layer membrane facades and materials under a void-free covering with a minimum thickness of 0.5 mm (RF1), 3 mm (RF2) or 5 mm (RF3).
Description
RF4 materials are permitted only void-free and encapsulated on all sides K 30, with exceptions for protective insulation layers, vapour barriers, laminations and thin pipe-insulation sheathing. Not yet checkable: the model does not carry the reaction-to-fire group (RF1 - RF4, cr) of materials.
Source
VKF-Brandschutzrichtlinie 14-15 Verwendung von Baustoffen (2015) (p. 4)
More rules for Fire protection directive 14-15 Use of building materials
-
VKF-14-15-010
Vertical escape routes: reaction to fire of linings and structures
In vertical escape routes (stairwells) of low and medium-height buildings with a structural concept, walls and floors with fire resistance, wall and ceiling linings, classified systems, stretched ceilings and stair and landing structures are made of RF1 materials; floor coverings are at least RF2.
-
VKF-14-15-011
Horizontal escape routes: reaction to fire of linings
In horizontal escape routes of low and medium-height buildings, wall and ceiling linings and classified systems are made of RF1 materials with a structural concept and of RF2 with an extinguishing-system concept; stretched ceilings are RF1 or RF2, one group lower where more than 5 m above walkable areas.
-
VKF-14-15-012
Escape routes: combustible area share at most 10 %
In escape routes, the area share of combustible materials such as luminous panels, pin boards, linings or balustrade infills is at most 10 % of the stairwell floor area per storey or of the floor area of the horizontal escape route. Partial areas are at most 2 m² and keep at least 2 m distance from each other.