Rule Fire protection directive 26-15 Hazardous substances
Storage concept, substance segregation in separate fire compartments and hazard signs
VKF-26-15-008
pragmaticBIM.ch/vkf-26-15-008
A storage concept is drawn up for stores with hazardous substances (inventory, location, type and container, structural, technical and organisational measures).
Description
Substances that can react dangerously with each other, those with special fire behaviour or those that endanger people in a fire go into separate, suitably built fire compartments; for substances of different hazard classes in the same room, measures follow the most hazardous product. The annex allows, up to 1,000 kg or l in the same compartment, storing together, apart or separately depending on the pair of substances; storing apart means a screen wall of at least EI 60 or 2.5 m distance. Fire and explosion hazard and the smoking ban are signed visibly. Not yet checkable: the model does not show substance classification, stored quantity, type and location of hazardous substances.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 8)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-009
Gas cylinders: not in escape routes, ventilated, from 200 l cylinder volume outdoors or in a separate fire compartment
Gas cylinders are protected against excessive heating, mechanical damage and falling over and are not stored together with highly flammable or self-igniting substances. In escape routes they are neither connected nor stored; rooms with connected or stored cylinders are sufficiently ventilated.
-
VKF-26-15-010
Cryogenic tanks outdoors with a 5 m protected zone EI 60; liquefied petroleum gas not in basements
Cryogenic tanks (vacuum-insulated tanks for deep-cooled liquefied oxidising or asphyxiant gases) stand outdoors and not in depressions.
-
VKF-26-15-011
Aerosol packs: stored apart, below 50 °C, from 100 l behind a grille, flammable ones ventilated
Aerosol packs (spray cans) are stored in rooms with low fire risk, locally separated from other stored goods, and kept and used so that they do not warm above 50 °C. Above 100 l they stand behind a grille (e.g. pallet with cage frame, mesh box).