Rule Fire protection directive 26-15 Hazardous substances
Gas cylinders: not in escape routes, ventilated, from 200 l cylinder volume outdoors or in a separate fire compartment
VKF-26-15-009
pragmaticBIM.ch/vkf-26-15-009
Gas cylinders are protected against excessive heating, mechanical damage and falling over and are not stored together with highly flammable or self-igniting substances. In escape routes they are neither connected nor stored; rooms with connected or stored cylinders are sufficiently ventilated.
Description
From 200 l cylinder volume they stand outdoors, in a separate fire compartment without additional fire loads, or in cabinets to SN EN 14470-2 that reach at least the fire resistance of the compartment. Not yet checkable: the model does not show gas type, cylinder volume, stored quantity and location of gas storage.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 8)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-010
Cryogenic tanks outdoors with a 5 m protected zone EI 60; liquefied petroleum gas not in basements
Cryogenic tanks (vacuum-insulated tanks for deep-cooled liquefied oxidising or asphyxiant gases) stand outdoors and not in depressions.
-
VKF-26-15-011
Aerosol packs: stored apart, below 50 °C, from 100 l behind a grille, flammable ones ventilated
Aerosol packs (spray cans) are stored in rooms with low fire risk, locally separated from other stored goods, and kept and used so that they do not warm above 50 °C. Above 100 l they stand behind a grille (e.g. pallet with cage frame, mesh box).
-
VKF-26-15-012
Combustible liquids: prevent spreading, vapours not into lower rooms, flash point ≤ 23 °C only in permitted containers
Leaking combustible liquids must not spread (e.g. raised door thresholds, drainage channels, separators, drip trays), and their vapours must not reach lower rooms, sewers, shafts or pits. Heating devices are thermally secured; no heating with open flames or unprotected heat sources.