Rule Fire protection directive 26-15 Hazardous substances
Cryogenic tanks outdoors with a 5 m protected zone EI 60; liquefied petroleum gas not in basements
VKF-26-15-010
pragmaticBIM.ch/vkf-26-15-010
Cryogenic tanks (vacuum-insulated tanks for deep-cooled liquefied oxidising or asphyxiant gases) stand outdoors and not in depressions.
Description
Within 5 m of cryogenic tanks with oxidising gases, building facades are free of openings, stable and at least EI 60 of RF1 materials, and no combustible materials are present; a suitable screen wall can reduce the distance. Liquefied petroleum gas (LPG) is not stored in basement storeys. Not yet checkable: the model does not show gas type, cylinder volume, stored quantity and location of gas storage.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 9)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-011
Aerosol packs: stored apart, below 50 °C, from 100 l behind a grille, flammable ones ventilated
Aerosol packs (spray cans) are stored in rooms with low fire risk, locally separated from other stored goods, and kept and used so that they do not warm above 50 °C. Above 100 l they stand behind a grille (e.g. pallet with cage frame, mesh box).
-
VKF-26-15-012
Combustible liquids: prevent spreading, vapours not into lower rooms, flash point ≤ 23 °C only in permitted containers
Leaking combustible liquids must not spread (e.g. raised door thresholds, drainage channels, separators, drip trays), and their vapours must not reach lower rooms, sewers, shafts or pits. Heating devices are thermally secured; no heating with open flames or unprotected heat sources.
-
VKF-26-15-013
Storage rooms for combustible liquids: EI 30 doors, access opening at least 0.7 × 1 m with an EI 30 cover
Storage rooms for combustible liquids are closed off from other rooms with EI 30 doors. Access to tank rooms is by openings of at least 0.7 × 1 m, closed with EI 30 covers.