Rule Fire protection directive 26-15 Hazardous substances
Aerosol packs: stored apart, below 50 °C, from 100 l behind a grille, flammable ones ventilated
VKF-26-15-011
pragmaticBIM.ch/vkf-26-15-011
Aerosol packs (spray cans) are stored in rooms with low fire risk, locally separated from other stored goods, and kept and used so that they do not warm above 50 °C. Above 100 l they stand behind a grille (e.g. pallet with cage frame, mesh box).
Description
Rooms with aerosol packs with flammable propellant or content are ventilated. Not yet checkable: the model does not show gas type, cylinder volume, stored quantity and location of gas storage.
Source
VKF-Brandschutzrichtlinie 26-15 Gefährliche Stoffe (2015) (p. 9)
More rules for Fire protection directive 26-15 Hazardous substances
-
VKF-26-15-012
Combustible liquids: prevent spreading, vapours not into lower rooms, flash point ≤ 23 °C only in permitted containers
Leaking combustible liquids must not spread (e.g. raised door thresholds, drainage channels, separators, drip trays), and their vapours must not reach lower rooms, sewers, shafts or pits. Heating devices are thermally secured; no heating with open flames or unprotected heat sources.
-
VKF-26-15-013
Storage rooms for combustible liquids: EI 30 doors, access opening at least 0.7 × 1 m with an EI 30 cover
Storage rooms for combustible liquids are closed off from other rooms with EI 30 doors. Access to tank rooms is by openings of at least 0.7 × 1 m, closed with EI 30 covers.
-
VKF-26-15-014
Containers and small tanks: requirement for room or cabinet by stored quantity (25 l to over 2,000 l) and flash point
For combustible liquids with a flash point up to 60 °C, per compartment: up to 25 l a room of any construction; 26 - 100 l an RF1 cabinet with collecting tray and marking; 101 - 450 l a room EI 30 with low fire risk; 451 - 2,000 l a room EI 60 without additional fire loads; above 2,000 l a room EI 90 without...