Rule Fire protection directive 25-15 Ventilation systems
Kitchen extract: grease separators, RF1 ducts, separate plant rooms from EI 60
VKF-25-15-016
pragmaticBIM.ch/vkf-25-15-016
Kitchen extract ducts are RF1 (heat-resistant) and have a grease separator or filter near the extraction point. In residential buildings RF1 is enough for hood extract; after the hood and before heat recovery a VKF-recognised shut-off device is installed.
Description
Commercial kitchens have separate units and ducts; outside the kitchen the extract ducts are EI 30 or more (matching the compartmentation). Fans stand in their own room of at least EI 60; for large extract volumes (above 4,000 or 12,000 m³/h) separate systems and rooms apply. Kitchen extract ducts in an installation shaft are separated from each other and from other installations with a 30-minute fire protection board of RF1. Not yet checkable: extract volume, kitchen type and grease separators are not captured in the model.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 9)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-017
Systems with air temperature above 85 °C: RF1 ducts and safety distances
At air temperatures above 85 °C the ventilation ducts are RF1 (heat-resistant) and keep a distance to combustible material: 0.1 m up to 100 °C, 0.2 m up to 200 °C, 0.4 m up to 400 °C. With a 30-minute cladding of RF1 (heat-resistant) the distances are halved.
-
VKF-25-15-018
Systems for explosion-hazard areas and aggressive media
Systems for fire and explosion hazard areas have separate units and ducts; if the units stand in another area they go in their own room with the fire resistance of the compartmentation, at least EI 60.
-
VKF-25-15-019
Ducts with increased requirements in an installation shaft: separation EI 30
Several ventilation ducts of systems with increased requirements (clauses 4.3.1 to 4.3.3) in the same installation shaft are separated storey by storey and compartment by compartment with a 30-minute fire protection board of RF1; RF1 ducts may instead be clad individually with EI 30 of RF1.