Rule Fire protection directive 25-15 Ventilation systems
Ducts with increased requirements in an installation shaft: separation EI 30
VKF-25-15-019
pragmaticBIM.ch/vkf-25-15-019
Several ventilation ducts of systems with increased requirements (clauses 4.3.1 to 4.3.3) in the same installation shaft are separated storey by storey and compartment by compartment with a 30-minute fire protection board of RF1; RF1 ducts may instead be clad individually with EI 30 of RF1.
Description
From other installations in the shaft they are likewise separated with such a board. Several combustible ducts in the same shaft need no separation if deluge or sprinkler nozzles are installed in the shaft. Not yet checkable: the model does not show which ducts share a shaft or how they are separated.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 11)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-001
Air-handling units serving several ventilation sections: separate room with EI 30 and EI 30 doors
Units that serve several ventilation sections are installed in a separate room. Its enclosure matches the fire resistance of the use-related compartmentation, but at least EI 30; the doors are also EI 30.
-
VKF-25-15-002
Outdoor air and exhaust air: safe intake and discharge
Outdoor air is taken directly from the open so that no combustible gases or vapours are drawn in. Exhaust-air ducts discharge to the open so that escaping fire gases and flames do not endanger the surroundings and cannot reach the outdoor-air intake.
-
VKF-25-15-020
Cleaning, inspection and maintenance of ventilation systems and fire dampers
Ventilation systems are cleaned and maintained so that they are always ready for operation and no fire hazard arises. Fire dampers and fire-case controls are inspected periodically.