Rule Fire protection directive 25-15 Ventilation systems
Systems with air temperature above 85 °C: RF1 ducts and safety distances
VKF-25-15-017
pragmaticBIM.ch/vkf-25-15-017
At air temperatures above 85 °C the ventilation ducts are RF1 (heat-resistant) and keep a distance to combustible material: 0.1 m up to 100 °C, 0.2 m up to 200 °C, 0.4 m up to 400 °C. With a 30-minute cladding of RF1 (heat-resistant) the distances are halved.
Description
The exhaust of pizza, baking and bake-off ovens is connected to a system designed for the raised temperature. Not yet checkable: the air temperature of the system and the distance to combustible components are not held in the model.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 10)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-018
Systems for explosion-hazard areas and aggressive media
Systems for fire and explosion hazard areas have separate units and ducts; if the units stand in another area they go in their own room with the fire resistance of the compartmentation, at least EI 60.
-
VKF-25-15-019
Ducts with increased requirements in an installation shaft: separation EI 30
Several ventilation ducts of systems with increased requirements (clauses 4.3.1 to 4.3.3) in the same installation shaft are separated storey by storey and compartment by compartment with a 30-minute fire protection board of RF1; RF1 ducts may instead be clad individually with EI 30 of RF1.
-
VKF-25-15-020
Cleaning, inspection and maintenance of ventilation systems and fire dampers
Ventilation systems are cleaned and maintained so that they are always ready for operation and no fire hazard arises. Fire dampers and fire-case controls are inspected periodically.