Rule Fire protection directive 25-15 Ventilation systems
Systems for explosion-hazard areas and aggressive media
VKF-25-15-018
pragmaticBIM.ch/vkf-25-15-018
Systems for fire and explosion hazard areas have separate units and ducts; if the units stand in another area they go in their own room with the fire resistance of the compartmentation, at least EI 60.
Description
Outside and at roof penetrations the ducts keep 0.2 m from combustible material; fans near the discharge point produce no sparks. For aggressive media at least RF2 is enough for air-carrying parts; combustible ducts run outside the building or in shafts of EI 60 made of RF1 (heat-resistant). Not yet checkable: explosion-hazard areas and aggressive media are not modelled as a room property.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 10)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-001
Air-handling units serving several ventilation sections: separate room with EI 30 and EI 30 doors
Units that serve several ventilation sections are installed in a separate room. Its enclosure matches the fire resistance of the use-related compartmentation, but at least EI 30; the doors are also EI 30.
-
VKF-25-15-019
Ducts with increased requirements in an installation shaft: separation EI 30
Several ventilation ducts of systems with increased requirements (clauses 4.3.1 to 4.3.3) in the same installation shaft are separated storey by storey and compartment by compartment with a 30-minute fire protection board of RF1; RF1 ducts may instead be clad individually with EI 30 of RF1.
-
VKF-25-15-020
Cleaning, inspection and maintenance of ventilation systems and fire dampers
Ventilation systems are cleaned and maintained so that they are always ready for operation and no fire hazard arises. Fire dampers and fire-case controls are inspected periodically.