Rule Fire protection directive 25-15 Ventilation systems

Systems for explosion-hazard areas and aggressive media

VKF-25-15-018 pragmaticBIM.ch/vkf-25-15-018

Systems for fire and explosion hazard areas have separate units and ducts; if the units stand in another area they go in their own room with the fire resistance of the compartmentation, at least EI 60.

Description

Outside and at roof penetrations the ducts keep 0.2 m from combustible material; fans near the discharge point produce no sparks. For aggressive media at least RF2 is enough for air-carrying parts; combustible ducts run outside the building or in shafts of EI 60 made of RF1 (heat-resistant). Not yet checkable: explosion-hazard areas and aggressive media are not modelled as a room property.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 10)