Rule Fire protection directive 25-15 Ventilation systems
Duct penetration through compartment-forming components: firestop EI 30 or RF1 filling
VKF-25-15-010
pragmaticBIM.ch/vkf-25-15-010
The recess between the ventilation duct and the compartment-forming component is, allowing for thermal expansion, either filled tightly with RF1 materials (e.g. mortar, plaster) or closed with a firestop system that reaches EI 30 in compartment-forming walls and floors.
Description
For rooms or compartments with a high fire load or fire hazard, the firestop system has the same fire resistance as the surrounding walls and floors. Not yet checkable: the model does not consistently link ducts and firestops to the components they pass through.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 7)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-011
Fire dampers: at least EI 30-S, actuator, thermal release, self-closing
Fire dampers prevent fire and smoke from spreading through ventilation systems and are rated at least EI 30-S. They are fixed according to the declaration of performance or VKF technical information and the manufacturer's instructions, and are accessible and inspectable from outside.
-
VKF-25-15-012
Fire dampers where ducts cross fire compartments and ventilation sections
Fire dampers are placed where ventilation ducts pass through fire walls and compartment-forming walls and floors, and where ducts without openings run through other ventilation sections without having the required fire resistance themselves.
-
VKF-25-15-013
Omitting fire dampers: permitted exceptions
Fire dampers can be omitted where fire compartments can be combined structurally into ventilation sections; in office and school buildings with a ventilation-section area up to 1,200 m²; in accommodation and residential buildings up to 600 m²; for ventilation of wet cells; with separate duct routing up to the...