Rule Fire protection directive 25-15 Ventilation systems

Duct penetration through compartment-forming components: firestop EI 30 or RF1 filling

VKF-25-15-010 pragmaticBIM.ch/vkf-25-15-010

The recess between the ventilation duct and the compartment-forming component is, allowing for thermal expansion, either filled tightly with RF1 materials (e.g. mortar, plaster) or closed with a firestop system that reaches EI 30 in compartment-forming walls and floors.

Description

For rooms or compartments with a high fire load or fire hazard, the firestop system has the same fire resistance as the surrounding walls and floors. Not yet checkable: the model does not consistently link ducts and firestops to the components they pass through.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 7)