Rule Fire protection directive 25-15 Ventilation systems

Omitting fire dampers: permitted exceptions

VKF-25-15-013 pragmaticBIM.ch/vkf-25-15-013

Fire dampers can be omitted where fire compartments can be combined structurally into ventilation sections; in office and school buildings with a ventilation-section area up to 1,200 m²; in accommodation and residential buildings up to 600 m²; for ventilation of wet cells; with separate duct routing up to the...

Description

Fire dampers can be omitted where fire compartments can be combined structurally into ventilation sections; in office and school buildings with a ventilation-section area up to 1,200 m²; in accommodation and residential buildings up to 600 m²; for ventilation of wet cells; with separate duct routing up to the ventilation plant room; in high-rise buildings for wet-cell and dwelling-kitchen ventilation with no more than 5 connected storeys per riser; and between ventilation plant rooms and installation shafts. Not yet checkable: ventilation-section area, storeys per riser and duct routing to the plant room are not derived in the model.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 8)