Rule Fire protection directive 25-15 Ventilation systems

Fire dampers: at least EI 30-S, actuator, thermal release, self-closing

VKF-25-15-011 pragmaticBIM.ch/vkf-25-15-011

Fire dampers prevent fire and smoke from spreading through ventilation systems and are rated at least EI 30-S. They are fixed according to the declaration of performance or VKF technical information and the manufacturer's instructions, and are accessible and inspectable from outside.

Description

Each damper has an actuator and a thermal release device and closes by itself when the system is switched off, when the thermal release responds and when the actuator fails. They are not used as control dampers. Shut-off devices have no actuator for repeated opening and closing. Not yet checkable: dampers carry no fire resistance class with smoke tightness, no fail-safe position and no actuator or release type.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 7)