Rule Fire protection directive 25-15 Ventilation systems
Fire dampers where ducts cross fire compartments and ventilation sections
VKF-25-15-012
pragmaticBIM.ch/vkf-25-15-012
Fire dampers are placed where ventilation ducts pass through fire walls and compartment-forming walls and floors, and where ducts without openings run through other ventilation sections without having the required fire resistance themselves.
Description
Shut-off devices must not replace required fire dampers; their use follows the declaration of performance or VKF technical information. Not yet checkable: the model holds no crossing of duct and compartment-forming component and no assignment of a damper to that spot.
Source
VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 8)
More rules for Fire protection directive 25-15 Ventilation systems
-
VKF-25-15-013
Omitting fire dampers: permitted exceptions
Fire dampers can be omitted where fire compartments can be combined structurally into ventilation sections; in office and school buildings with a ventilation-section area up to 1,200 m²; in accommodation and residential buildings up to 600 m²; for ventilation of wet cells; with separate duct routing up to the...
-
VKF-25-15-014
Fire-case control: system switches off automatically on alarm, otherwise manual switch-off
Ventilation systems switch off automatically when fire detection or extinguishing systems, duct smoke detectors or the thermal release of fire dampers respond. Where such devices are missing, the systems can be switched off by hand at an easily accessible place.
-
VKF-25-15-015
Escape routes: no open air routing, ventilation separate or with fire dampers
Escape routes do not replace ventilation ducts for open air routing. Compartment-forming escape routes are in principle ventilated separately from other ventilation systems; otherwise fire dampers belong in the compartment-forming walls, with storey-by-storey subdivision, separate ducts or separate systems.