Rule Fire protection directive 25-15 Ventilation systems

Fire dampers where ducts cross fire compartments and ventilation sections

VKF-25-15-012 pragmaticBIM.ch/vkf-25-15-012

Fire dampers are placed where ventilation ducts pass through fire walls and compartment-forming walls and floors, and where ducts without openings run through other ventilation sections without having the required fire resistance themselves.

Description

Shut-off devices must not replace required fire dampers; their use follows the declaration of performance or VKF technical information. Not yet checkable: the model holds no crossing of duct and compartment-forming component and no assignment of a damper to that spot.

Source

VKF-Brandschutzrichtlinie 25-15 Lufttechnische Anlagen (2015) (p. 8)