Rule Fire protection directive 24-15 Heating plant

Solid fuels: daily consumption in the installation room, store EI 60, at most 10 m³ in the boiler room

VKF-24-15-017 pragmaticBIM.ch/vkf-24-15-017

Only a day's consumption may be stored in the installation room, shielded from the unit; larger quantities go into other rooms or outdoors. In single-family houses wood or coal up to 5 m³ is allowed in rooms of any construction.

Description

Built-in or attached storage rooms are separated with EI 60. In separate boiler rooms with EI 60, up to 10 m³ may be kept behind a barrier 1 m from the unit. Easily ignitable kindling is stored only in closed RF1 containers. Not yet checkable: the model does not show fuel type, stored quantity and tank volume.

Source

VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 15)

More rules for Fire protection directive 24-15 Heating plant