Rule Fire protection directive 24-15 Heating plant
Heating oil: up to 4,000 l small tanks or 8,000 l steel tanks in a boiler room EI 60, delivery systems not in escape routes
VKF-24-15-018
pragmaticBIM.ch/vkf-24-15-018
In separate boiler rooms with EI 60, heating oil up to 4,000 l in small tanks or up to 8,000 l in steel tanks may be stored; the directive on hazardous substances applies in addition.
Description
Intermediate and service tanks and delivery pumps are not placed in escape routes, tanks in the roof space have a thermal cut-off above 70 °C, and the oil does not warm above 50 °C. Oil pipes of combustible material run outside the tank or installation room in RF1 protective tubes, through other compartments additionally clad with EI 30. Not yet checkable: the model does not show fuel type, stored quantity and tank volume.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 16)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-001
Heating plant: safe operation, verified products and permanent marking
Heating plant is built and installed so that it operates safely and damage in case of a fault stays limited; all parts withstand the thermal, chemical and mechanical stresses.
-
VKF-24-15-002
Ban on installing heat generators in escape routes, explosion-hazard rooms and rooms with high fire load
Heat generators must not be installed in escape routes, in rooms and zones with fire or explosion hazard, or in rooms with large and very large fire load. Not yet checkable: the model does not show nominal heat output, fuel, type of installation and fire resistance of the boiler room.
-
VKF-24-15-019
Operational readiness and maintenance of heating plant
Owners or operators ensure that heating plant is maintained as intended and is ready for operation at all times.