Rule Fire protection directive 24-15 Heating plant

Heating oil: up to 4,000 l small tanks or 8,000 l steel tanks in a boiler room EI 60, delivery systems not in escape routes

VKF-24-15-018 pragmaticBIM.ch/vkf-24-15-018

In separate boiler rooms with EI 60, heating oil up to 4,000 l in small tanks or up to 8,000 l in steel tanks may be stored; the directive on hazardous substances applies in addition.

Description

Intermediate and service tanks and delivery pumps are not placed in escape routes, tanks in the roof space have a thermal cut-off above 70 °C, and the oil does not warm above 50 °C. Oil pipes of combustible material run outside the tank or installation room in RF1 protective tubes, through other compartments additionally clad with EI 30. Not yet checkable: the model does not show fuel type, stored quantity and tank volume.

Source

VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 16)