Rule Fire protection directive 24-15 Heating plant
Flue systems through compartments: EI 60 vertically, compartment value horizontally, distance to combustibles, fill-in
VKF-24-15-015
pragmaticBIM.ch/vkf-24-15-015
Flue systems running vertically through several compartments have EI 60 of heat-resistant RF1 outside the installation room or sit in such a fire protection element, in single-family houses and flats EI 30; horizontally the fire resistance of the compartment applies.
Description
In a shared shaft an EI 30 board separates combustible from RF1 flue systems. A clearance to combustibles applies so that adjoining materials reach at most 85 °C; penetrations through combustible constructions are filled with RF1. Connecting pipes are not concealed. Not yet checkable: the model holds no flue system with classification, routing, minimum height above roof and clearance.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 13)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-016
Explosion flaps, flue fans and cleaning openings
For fuels prone to deflagration, such as fine-grained coal or wood chips, explosion flaps belong in the flue system, in the boiler room close to the connecting pipe entry and at least the cross-section of the flue. Flue fans create positive pressure only if the system is approved for it.
-
VKF-24-15-017
Solid fuels: daily consumption in the installation room, store EI 60, at most 10 m³ in the boiler room
Only a day's consumption may be stored in the installation room, shielded from the unit; larger quantities go into other rooms or outdoors. In single-family houses wood or coal up to 5 m³ is allowed in rooms of any construction.
-
VKF-24-15-018
Heating oil: up to 4,000 l small tanks or 8,000 l steel tanks in a boiler room EI 60, delivery systems not in escape routes
In separate boiler rooms with EI 60, heating oil up to 4,000 l in small tanks or up to 8,000 l in steel tanks may be stored; the directive on hazardous substances applies in addition.