Rule Fire protection directive 24-15 Heating plant
Explosion flaps, flue fans and cleaning openings
VKF-24-15-016
pragmaticBIM.ch/vkf-24-15-016
For fuels prone to deflagration, such as fine-grained coal or wood chips, explosion flaps belong in the flue system, in the boiler room close to the connecting pipe entry and at least the cross-section of the flue. Flue fans create positive pressure only if the system is approved for it.
Description
Flue systems have openings for inspection and cleaning, accessories can be removed easily; in rooms with fire or explosion hazard such openings are not permitted. Not yet checkable: the model holds no flue system with classification, routing, minimum height above roof and clearance.
Source
VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 15)
More rules for Fire protection directive 24-15 Heating plant
-
VKF-24-15-017
Solid fuels: daily consumption in the installation room, store EI 60, at most 10 m³ in the boiler room
Only a day's consumption may be stored in the installation room, shielded from the unit; larger quantities go into other rooms or outdoors. In single-family houses wood or coal up to 5 m³ is allowed in rooms of any construction.
-
VKF-24-15-018
Heating oil: up to 4,000 l small tanks or 8,000 l steel tanks in a boiler room EI 60, delivery systems not in escape routes
In separate boiler rooms with EI 60, heating oil up to 4,000 l in small tanks or up to 8,000 l in steel tanks may be stored; the directive on hazardous substances applies in addition.
-
VKF-24-15-019
Operational readiness and maintenance of heating plant
Owners or operators ensure that heating plant is maintained as intended and is ready for operation at all times.