Rule Fire protection directive 24-15 Heating plant

Explosion flaps, flue fans and cleaning openings

VKF-24-15-016 pragmaticBIM.ch/vkf-24-15-016

For fuels prone to deflagration, such as fine-grained coal or wood chips, explosion flaps belong in the flue system, in the boiler room close to the connecting pipe entry and at least the cross-section of the flue. Flue fans create positive pressure only if the system is approved for it.

Description

Flue systems have openings for inspection and cleaning, accessories can be removed easily; in rooms with fire or explosion hazard such openings are not permitted. Not yet checkable: the model holds no flue system with classification, routing, minimum height above roof and clearance.

Source

VKF-Brandschutzrichtlinie 24-15 Wärmetechnische Anlagen (2015) (p. 15)