Rule Fire protection directive 21-15 Smoke and heat exhaust systems

Hot-gas fans: temperature resistance and installation room of at least EI 30

VKF-21-15-010 pragmaticBIM.ch/vkf-21-15-010

Suitable hot-gas fans are used to extract the smoke gases; they withstand at least 400 °C for the required operating time, in compartments with a water-based extinguishing system and in vertical escape routes at least 200 °C.

Description

If higher temperatures are expected, the value is raised in agreement with the fire protection authority. Except in the room to be cleared or outdoors, they stand in a separate room with the fire resistance of the use-related compartmentation, at least EI 30. Not yet checkable: the model does not show the functional duration of plant parts or the fire resistance of the enclosure.

Source

VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 9)