Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Hot-gas fans: temperature resistance and installation room of at least EI 30
VKF-21-15-010
pragmaticBIM.ch/vkf-21-15-010
Suitable hot-gas fans are used to extract the smoke gases; they withstand at least 400 °C for the required operating time, in compartments with a water-based extinguishing system and in vertical escape routes at least 200 °C.
Description
If higher temperatures are expected, the value is raised in agreement with the fire protection authority. Except in the room to be cleared or outdoors, they stand in a separate room with the fire resistance of the use-related compartmentation, at least EI 30. Not yet checkable: the model does not show the functional duration of plant parts or the fire resistance of the enclosure.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 9)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-011
Smoke-extraction ducts and dampers: fire resistance of the crossed compartment, dampers at least EI 30
Shafts and ducts withstand the expected stresses and prevent fire and smoke spread when hot fire gases are extracted; length expansion is taken up by fixed points and compensators, and plastic anchors are not permitted for exhaust ducts.
-
VKF-21-15-012
Make-up air: inflow openings near the floor, matched to the exhaust openings
Installing a smoke and heat exhaust system requires that the make-up air needed for effective extraction can flow in. Inflow openings, such as façade openings, doors, gates or windows, are placed near the floor and matched to exhaust openings and extract volumes.
-
VKF-21-15-013
Operation and triggering: manual release at a safe location, automatic release with performance proof
Systems can be started by hand from a location that is safe in case of fire; the control points show operating, fault and out-of-service states. The fire protection authority can additionally require automatic release.