Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Operation and triggering: manual release at a safe location, automatic release with performance proof
VKF-21-15-013
pragmaticBIM.ch/vkf-21-15-013
Systems can be started by hand from a location that is safe in case of fire; the control points show operating, fault and out-of-service states. The fire protection authority can additionally require automatic release.
Description
Systems with performance proof start automatically, for protection of people through a fire alarm system, for protection of property also through a sprinkler system, and can be switched on and off by hand by the fire brigade. Where neither a fire alarm nor a sprinkler system exists, fire detectors cover at least the affected compartment to ensure activation. Not yet checkable: the model holds no trigger and control points of the system and no power source for safety purposes.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 10)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-014
Power supply for safety purposes independent of the general supply
Smoke and heat exhaust systems and smoke-protection pressurization systems are connected to suitable power sources that are independent of the general power supply. Not yet checkable: the model holds no trigger and control points of the system and no power source for safety purposes.
-
VKF-21-15-015
Use of ventilation systems for smoke extraction only if RWA requirements are met
Ventilation and air-conditioning systems may be used for smoke and heat extraction only if the affected plant parts meet the requirements for smoke and heat exhaust systems. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.
-
VKF-21-15-016
Concepts: fire-brigade fans down to the 1st basement, natural systems not below ground, extraction under the ceiling
Smoke clearance with fire-brigade fans assumes response forces on site within 15 minutes of the alarm, needs inlet openings for setting up the fans in addition to the exhaust openings, and below ground is permitted only down to the 1st basement unless supply air comes from outdoors on the same level.