Rule Fire protection directive 21-15 Smoke and heat exhaust systems

Operation and triggering: manual release at a safe location, automatic release with performance proof

VKF-21-15-013 pragmaticBIM.ch/vkf-21-15-013

Systems can be started by hand from a location that is safe in case of fire; the control points show operating, fault and out-of-service states. The fire protection authority can additionally require automatic release.

Description

Systems with performance proof start automatically, for protection of people through a fire alarm system, for protection of property also through a sprinkler system, and can be switched on and off by hand by the fire brigade. Where neither a fire alarm nor a sprinkler system exists, fire detectors cover at least the affected compartment to ensure activation. Not yet checkable: the model holds no trigger and control points of the system and no power source for safety purposes.

Source

VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 10)