Rule Fire protection directive 21-15 Smoke and heat exhaust systems

Make-up air: inflow openings near the floor, matched to the exhaust openings

VKF-21-15-012 pragmaticBIM.ch/vkf-21-15-012

Installing a smoke and heat exhaust system requires that the make-up air needed for effective extraction can flow in. Inflow openings, such as façade openings, doors, gates or windows, are placed near the floor and matched to exhaust openings and extract volumes.

Description

For mechanical systems without performance proof, inflow velocities up to about 3 m/s are permitted, and the pressure conditions must not impair passage through escape doors. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.

Source

VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 9)