Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Make-up air: inflow openings near the floor, matched to the exhaust openings
VKF-21-15-012
pragmaticBIM.ch/vkf-21-15-012
Installing a smoke and heat exhaust system requires that the make-up air needed for effective extraction can flow in. Inflow openings, such as façade openings, doors, gates or windows, are placed near the floor and matched to exhaust openings and extract volumes.
Description
For mechanical systems without performance proof, inflow velocities up to about 3 m/s are permitted, and the pressure conditions must not impair passage through escape doors. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 9)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-013
Operation and triggering: manual release at a safe location, automatic release with performance proof
Systems can be started by hand from a location that is safe in case of fire; the control points show operating, fault and out-of-service states. The fire protection authority can additionally require automatic release.
-
VKF-21-15-014
Power supply for safety purposes independent of the general supply
Smoke and heat exhaust systems and smoke-protection pressurization systems are connected to suitable power sources that are independent of the general power supply. Not yet checkable: the model holds no trigger and control points of the system and no power source for safety purposes.
-
VKF-21-15-015
Use of ventilation systems for smoke extraction only if RWA requirements are met
Ventilation and air-conditioning systems may be used for smoke and heat extraction only if the affected plant parts meet the requirements for smoke and heat exhaust systems. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.