Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Smoke-extraction ducts and dampers: fire resistance of the crossed compartment, dampers at least EI 30
VKF-21-15-011
pragmaticBIM.ch/vkf-21-15-011
Shafts and ducts withstand the expected stresses and prevent fire and smoke spread when hot fire gases are extracted; length expansion is taken up by fixed points and compensators, and plastic anchors are not permitted for exhaust ducts.
Description
Where they pass through other fire compartments they have the fire resistance required there. Smoke-extraction dampers for selective control have the fire resistance of the use-related compartmentation, at least EI 30. Not yet checkable: the model does not show the functional duration of plant parts or the fire resistance of the enclosure.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 9)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-012
Make-up air: inflow openings near the floor, matched to the exhaust openings
Installing a smoke and heat exhaust system requires that the make-up air needed for effective extraction can flow in. Inflow openings, such as façade openings, doors, gates or windows, are placed near the floor and matched to exhaust openings and extract volumes.
-
VKF-21-15-013
Operation and triggering: manual release at a safe location, automatic release with performance proof
Systems can be started by hand from a location that is safe in case of fire; the control points show operating, fault and out-of-service states. The fire protection authority can additionally require automatic release.
-
VKF-21-15-014
Power supply for safety purposes independent of the general supply
Smoke and heat exhaust systems and smoke-protection pressurization systems are connected to suitable power sources that are independent of the general power supply. Not yet checkable: the model holds no trigger and control points of the system and no power source for safety purposes.