Rule Fire protection directive 21-15 Smoke and heat exhaust systems
Exhaust openings: highest point, on façades evenly on two opposite sides
VKF-21-15-009
pragmaticBIM.ch/vkf-21-15-009
Exhaust openings are placed so that effective smoke clearance is possible without danger to people and buildings, at the highest point of the room, for example in the roof or in the ceiling or roof zone of the façades.
Description
If they cannot be built into the roof, they are distributed evenly over two façades that are as far as possible opposite each other. Individual openings for clearance with fire-brigade fans measure at least 0.5 m² with at least 0.1 m opening width. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.
Source
VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 9)
More rules for Fire protection directive 21-15 Smoke and heat exhaust systems
-
VKF-21-15-010
Hot-gas fans: temperature resistance and installation room of at least EI 30
Suitable hot-gas fans are used to extract the smoke gases; they withstand at least 400 °C for the required operating time, in compartments with a water-based extinguishing system and in vertical escape routes at least 200 °C.
-
VKF-21-15-011
Smoke-extraction ducts and dampers: fire resistance of the crossed compartment, dampers at least EI 30
Shafts and ducts withstand the expected stresses and prevent fire and smoke spread when hot fire gases are extracted; length expansion is taken up by fixed points and compensators, and plastic anchors are not permitted for exhaust ducts.
-
VKF-21-15-012
Make-up air: inflow openings near the floor, matched to the exhaust openings
Installing a smoke and heat exhaust system requires that the make-up air needed for effective extraction can flow in. Inflow openings, such as façade openings, doors, gates or windows, are placed near the floor and matched to exhaust openings and extract volumes.