Rule Fire protection directive 21-15 Smoke and heat exhaust systems

Exhaust openings: highest point, on façades evenly on two opposite sides

VKF-21-15-009 pragmaticBIM.ch/vkf-21-15-009

Exhaust openings are placed so that effective smoke clearance is possible without danger to people and buildings, at the highest point of the room, for example in the roof or in the ceiling or roof zone of the façades.

Description

If they cannot be built into the roof, they are distributed evenly over two façades that are as far as possible opposite each other. Individual openings for clearance with fire-brigade fans measure at least 0.5 m² with at least 0.1 m opening width. Not yet checkable: the model holds no smoke and heat exhaust system and no assignment of one to fire compartments.

Source

VKF-Brandschutzrichtlinie 21-15 Rauch- und Wärmeabzugsanlagen (2015) (p. 9)