Rule Fire protection directive 20-15 Fire alarm systems
Fire alarm control panel: safe location, monitored compartment, several panels in a room with EI 30
VKF-20-15-010
pragmaticBIM.ch/vkf-20-15-010
Fire alarm control panels and remote indicating panels stand at a safe, easily accessible location; the fire compartment of the panel is monitored.
Description
Several area panels at the same place go into a separate room with the fire resistance of the use-related compartmentation, at least EI 30, with EI 30 doors; further safety, small, low-voltage and telecommunication equipment may be housed there. Not yet checkable: the model holds no fire alarm control panel, no fire-brigade control unit and no fire-mode control as a system.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 8)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-011
Detector zones: fire location clearly identifiable, vertical shafts combined
The entire monitored area is divided into detector zones so that the fire location is shown quickly and unambiguously. Vertical escape routes, light, lift and installation shafts and tower-like structures form one common detector zone.
-
VKF-20-15-012
Manual call points in escape routes and hazardous areas, clearly visible, mounting height about 1.5 m
Manual call points are fitted clearly visibly in escape routes, for example at exits, passages, vertical escape routes and extinguishers, and in particularly hazardous areas.
-
VKF-20-15-013
Room indicator lamps at entrances to monitored rooms, at least 1.7 m above floor
So that the fire brigade can quickly locate the fire, indicator lamps are installed at entrances to monitored rooms and at raised floors and hollow ceilings, at least 1.7 m above floor.