Rule Fire protection directive 20-15 Fire alarm systems
Manual call points in escape routes and hazardous areas, clearly visible, mounting height about 1.5 m
VKF-20-15-012
pragmaticBIM.ch/vkf-20-15-012
Manual call points are fitted clearly visibly in escape routes, for example at exits, passages, vertical escape routes and extinguishers, and in particularly hazardous areas.
Description
They cannot be mistaken for light switches or lift buttons, are protected from mechanical damage and are mounted about 1.5 m high; where misuse is expected a sealable transparent cover is possible. Not yet checkable: the model holds detectors only as a device with location, without detector zone, monitored extent, mounting height and system.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 8)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-013
Room indicator lamps at entrances to monitored rooms, at least 1.7 m above floor
So that the fire brigade can quickly locate the fire, indicator lamps are installed at entrances to monitored rooms and at raised floors and hollow ceilings, at least 1.7 m above floor.
-
VKF-20-15-014
Special applications: detectors for high rooms, inaccessible places and special environments with consent
Detectors for special applications are used where point detectors are unsuitable or only partly suitable because of environmental influences or room conditions, for example outdoors, in cable tunnels, high halls, inaccessible voids, fume cupboards, silos or heritage buildings.
-
VKF-20-15-015
Specialist firm, documentation, switch-off, project, acceptance, inspection and review after 15 years
Fire alarm systems are planned, installed and maintained by VKF-recognised specialist firms, with components covered by a declaration of performance or VKF technical information. Orientation plans at the fire-brigade access and a logbook at the control panel are kept.