Rule Fire protection directive 20-15 Fire alarm systems
Detector zones: fire location clearly identifiable, vertical shafts combined
VKF-20-15-011
pragmaticBIM.ch/vkf-20-15-011
The entire monitored area is divided into detector zones so that the fire location is shown quickly and unambiguously. Vertical escape routes, light, lift and installation shafts and tower-like structures form one common detector zone.
Description
Detectors in voids above suspended ceilings, below raised floors and in ducts get their own zones or can be identified with a sub-area; manual call points in escape routes over more than two basements form separate zones for below and above. Not yet checkable: the model holds detectors only as a device with location, without detector zone, monitored extent, mounting height and system.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 8)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-012
Manual call points in escape routes and hazardous areas, clearly visible, mounting height about 1.5 m
Manual call points are fitted clearly visibly in escape routes, for example at exits, passages, vertical escape routes and extinguishers, and in particularly hazardous areas.
-
VKF-20-15-013
Room indicator lamps at entrances to monitored rooms, at least 1.7 m above floor
So that the fire brigade can quickly locate the fire, indicator lamps are installed at entrances to monitored rooms and at raised floors and hollow ceilings, at least 1.7 m above floor.
-
VKF-20-15-014
Special applications: detectors for high rooms, inaccessible places and special environments with consent
Detectors for special applications are used where point detectors are unsuitable or only partly suitable because of environmental influences or room conditions, for example outdoors, in cable tunnels, high halls, inaccessible voids, fume cupboards, silos or heritage buildings.