Rule Fire protection directive 20-15 Fire alarm systems

Room indicator lamps at entrances to monitored rooms, at least 1.7 m above floor

VKF-20-15-013 pragmaticBIM.ch/vkf-20-15-013

So that the fire brigade can quickly locate the fire, indicator lamps are installed at entrances to monitored rooms and at raised floors and hollow ceilings, at least 1.7 m above floor.

Description

Exceptions apply to permanently staffed premises with a guiding service, to bedroom storeys with labelled rooms, and to single rooms over 400 m² with their own detector zone and labelled access. Not yet checkable: the model holds detectors only as a device with location, without detector zone, monitored extent, mounting height and system.

Source

VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 9)