Rule Fire protection directive 20-15 Fire alarm systems
Room indicator lamps at entrances to monitored rooms, at least 1.7 m above floor
VKF-20-15-013
pragmaticBIM.ch/vkf-20-15-013
So that the fire brigade can quickly locate the fire, indicator lamps are installed at entrances to monitored rooms and at raised floors and hollow ceilings, at least 1.7 m above floor.
Description
Exceptions apply to permanently staffed premises with a guiding service, to bedroom storeys with labelled rooms, and to single rooms over 400 m² with their own detector zone and labelled access. Not yet checkable: the model holds detectors only as a device with location, without detector zone, monitored extent, mounting height and system.
Source
VKF-Brandschutzrichtlinie 20-15 Brandmeldeanlagen (2015) (p. 9)
More rules for Fire protection directive 20-15 Fire alarm systems
-
VKF-20-15-001
Fire alarm system by occupancy and use, special buildings on request
Depending on occupancy and use, buildings, installations or fire compartments are equipped with an adequately sized fire alarm system. It can be required for early alerting of rescue forces, for early activation of fire protection and building services systems, and in large and complex buildings.
-
VKF-20-15-014
Special applications: detectors for high rooms, inaccessible places and special environments with consent
Detectors for special applications are used where point detectors are unsuitable or only partly suitable because of environmental influences or room conditions, for example outdoors, in cable tunnels, high halls, inaccessible voids, fume cupboards, silos or heritage buildings.
-
VKF-20-15-015
Specialist firm, documentation, switch-off, project, acceptance, inspection and review after 15 years
Fire alarm systems are planned, installed and maintained by VKF-recognised specialist firms, with components covered by a declaration of performance or VKF technical information. Orientation plans at the fire-brigade access and a logbook at the control panel are kept.