Rule Fire protection directive 19-15 Sprinkler systems

Sprinkler control room: separate compartment of at least EI 30, between 1st upper floor and 1st basement, secured access

VKF-19-15-009 pragmaticBIM.ch/vkf-19-15-009

Sprinkler control rooms are located in separate fire compartments with the fire resistance of the use-related compartmentation, at least EI 30, with EI 30 doors.

Description

They have a safe, protected access, for example from outdoors or from a vertical escape route, and are located on the 1st upper floor, ground floor or 1st basement. Access and routes are marked; a suitable access system for the fire brigade is provided. Not yet checkable: the model does not show fire compartments, room types, fire load and fire resistance of the sprinkler control room.

Source

VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 7)