Rule Fire protection directive 19-15 Sprinkler systems

Water supply: reliable, connection to public network or own supply, nominal operating time 45 to 90 minutes

VKF-19-15-010 pragmaticBIM.ch/vkf-19-15-010

The sprinkler system requires a powerful, reliable water supply with the required connection capacity and pressure. It is connected to the public network in principle; if its capacity including the reserve for the fire brigade is insufficient, an own, combined or independent supply is needed.

Description

Faults are monitored where needed. With 15 minutes call-out and turn-out, the nominal operating time is 45 minutes up to 600 m², up to 60 minutes depending on area and room height, and 90 minutes for high-rise buildings up to 100 m. Not yet checkable: the model holds no sprinkler system with protected extent, control station and water supply.

Source

VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 7)