Rule Fire protection directive 19-15 Sprinkler systems

Shut-off valves only in the sprinkler control room; tested components

VKF-19-15-012 pragmaticBIM.ch/vkf-19-15-012

All plant parts are made of suitable materials and withstand the stresses; only sprinkler components with a declaration of performance or VKF technical information are used. Additives in the extinguishing water need a water-protection approval in addition to the fire protection one.

Description

Outside the sprinkler control room no shut-off valves are installed in principle; with the authority's consent they are permitted if mis-operation is excluded and the closed state is visible on the fire alarm system. Not yet checkable: the model holds no sprinkler system with protected extent, control station and water supply.

Source

VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 8)