Rule Fire protection directive 19-15 Sprinkler systems
Shut-off valves only in the sprinkler control room; tested components
VKF-19-15-012
pragmaticBIM.ch/vkf-19-15-012
All plant parts are made of suitable materials and withstand the stresses; only sprinkler components with a declaration of performance or VKF technical information are used. Additives in the extinguishing water need a water-protection approval in addition to the fire protection one.
Description
Outside the sprinkler control room no shut-off valves are installed in principle; with the authority's consent they are permitted if mis-operation is excluded and the closed state is visible on the fire alarm system. Not yet checkable: the model holds no sprinkler system with protected extent, control station and water supply.
Source
VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 8)
More rules for Fire protection directive 19-15 Sprinkler systems
-
VKF-19-15-001
Sprinkler system by occupancy and use, creditable against fire resistance and compartment size
Depending on occupancy and use, buildings, installations or fire compartments are equipped with an adequately sized sprinkler system. It can be taken into account when setting the fire resistance of structures and compartment-forming walls and floors and the permitted compartment size.
-
VKF-19-15-002
Industry, commerce, offices: sprinklers for exceeded compartments, fast fires, hazardous substances or high fire load
For industrial, commercial and office buildings the fire protection authority can require a sprinkler system if the permitted compartment sizes are exceeded and the system makes sense for the use, if fast-developing fires are expected, the ignition hazard is high, hazardous substances are handled or stored, or the...
-
VKF-19-15-013
Specialist firm, documentation, switch-off, project, acceptance, inspection and general overhaul
Sprinkler systems are planned, installed and maintained by VKF-recognised specialist firms and adapted on changes, extensions or changes of use. The control room holds the system documentation and a logbook, the fire-brigade access holds orientation plans.