Rule Fire protection directive 19-15 Sprinkler systems

Alerting and control: undelayed internal and external alarm via the fire alarm system

VKF-19-15-011 pragmaticBIM.ch/vkf-19-15-011

Every response triggers an internal and an external alarm without delay; the external one goes via a VKF-recognised fire alarm system to the public fire alarm receiving point. Faults are signalled visually and audibly and forwarded to a permanently staffed point.

Description

The sprinkler system may trigger fire protection equipment that does not serve life safety; flow switches serve only for signalling, not for triggering fire-mode controls. Fire-mode controls are documented and tested. Not yet checkable: the model holds no sprinkler system with protected extent, control station and water supply.

Source

VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 8)