Rule Fire protection directive 19-15 Sprinkler systems
Permitted exceptions from sprinkler protection
VKF-19-15-007
pragmaticBIM.ch/vkf-19-15-007
Sprinklers can be omitted, among others, in wet rooms without combustible stock, technical rooms with low fire hazard as a separate compartment, small rooms up to 4 m², cold rooms up to 50, 200 or 600 m² depending on insulation and separation, crawl spaces without fire load, vertical escape routes separated with...
Description
Sprinklers can be omitted, among others, in wet rooms without combustible stock, technical rooms with low fire hazard as a separate compartment, small rooms up to 4 m², cold rooms up to 50, 200 or 600 m² depending on insulation and separation, crawl spaces without fire load, vertical escape routes separated with fire resistance, lift shafts, voids above suspended ceilings or below raised floors with low fire load or height (below 0.3 m or 0.35 m) and intermediate climate zones of double façades. Not yet checkable: the model does not show fire compartments, room types, fire load and fire resistance of the sprinkler control room.
Source
VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 6)
More rules for Fire protection directive 19-15 Sprinkler systems
-
VKF-19-15-008
Water unsuitable: substitute measures with equivalent protection in the fire protection concept
Where water is not a suitable extinguishing agent, for example for silos with swelling contents, industrial furnaces and baths with increased hazard, substances that form combustible gases with water, or other endangered areas, substitute measures with equivalent protection are taken in agreement with the fire...
-
VKF-19-15-009
Sprinkler control room: separate compartment of at least EI 30, between 1st upper floor and 1st basement, secured access
Sprinkler control rooms are located in separate fire compartments with the fire resistance of the use-related compartmentation, at least EI 30, with EI 30 doors.
-
VKF-19-15-010
Water supply: reliable, connection to public network or own supply, nominal operating time 45 to 90 minutes
The sprinkler system requires a powerful, reliable water supply with the required connection capacity and pressure. It is connected to the public network in principle; if its capacity including the reserve for the fire brigade is insufficient, an own, combined or independent supply is needed.