Rule Fire protection directive 19-15 Sprinkler systems

Permitted exceptions from sprinkler protection

VKF-19-15-007 pragmaticBIM.ch/vkf-19-15-007

Sprinklers can be omitted, among others, in wet rooms without combustible stock, technical rooms with low fire hazard as a separate compartment, small rooms up to 4 m², cold rooms up to 50, 200 or 600 m² depending on insulation and separation, crawl spaces without fire load, vertical escape routes separated with...

Description

Sprinklers can be omitted, among others, in wet rooms without combustible stock, technical rooms with low fire hazard as a separate compartment, small rooms up to 4 m², cold rooms up to 50, 200 or 600 m² depending on insulation and separation, crawl spaces without fire load, vertical escape routes separated with fire resistance, lift shafts, voids above suspended ceilings or below raised floors with low fire load or height (below 0.3 m or 0.35 m) and intermediate climate zones of double façades. Not yet checkable: the model does not show fire compartments, room types, fire load and fire resistance of the sprinkler control room.

Source

VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 6)