Rule Fire protection directive 19-15 Sprinkler systems
Water unsuitable: substitute measures with equivalent protection in the fire protection concept
VKF-19-15-008
pragmaticBIM.ch/vkf-19-15-008
Where water is not a suitable extinguishing agent, for example for silos with swelling contents, industrial furnaces and baths with increased hazard, substances that form combustible gases with water, or other endangered areas, substitute measures with equivalent protection are taken in agreement with the fire...
Description
Where water is not a suitable extinguishing agent, for example for silos with swelling contents, industrial furnaces and baths with increased hazard, substances that form combustible gases with water, or other endangered areas, substitute measures with equivalent protection are taken in agreement with the fire protection authority, such as inerting, gas extinguishing system, protective hood or separation as a fire compartment. For dry systems and additives, the discharge delay must not reduce the extinguishing effect over the nominal operating time. Not yet checkable: the model does not show fire compartments, room types, fire load and fire resistance of the sprinkler control room.
Source
VKF-Brandschutzrichtlinie 19-15 Sprinkleranlagen (2015) (p. 6)
More rules for Fire protection directive 19-15 Sprinkler systems
-
VKF-19-15-009
Sprinkler control room: separate compartment of at least EI 30, between 1st upper floor and 1st basement, secured access
Sprinkler control rooms are located in separate fire compartments with the fire resistance of the use-related compartmentation, at least EI 30, with EI 30 doors.
-
VKF-19-15-010
Water supply: reliable, connection to public network or own supply, nominal operating time 45 to 90 minutes
The sprinkler system requires a powerful, reliable water supply with the required connection capacity and pressure. It is connected to the public network in principle; if its capacity including the reserve for the fire brigade is insufficient, an own, combined or independent supply is needed.
-
VKF-19-15-011
Alerting and control: undelayed internal and external alarm via the fire alarm system
Every response triggers an internal and an external alarm without delay; the external one goes via a VKF-recognised fire alarm system to the public fire alarm receiving point. Faults are signalled visually and audibly and forwarded to a permanently staffed point.