Rule Fire protection directive 16-15 Escape and rescue routes
Agriculture: two exits for stables above 200 m²
VKF-16-15-028
pragmaticBIM.ch/vkf-16-15-028
Stables with a floor area above 200 m² need at least two suitably placed, sufficiently large exits through which livestock can also be evacuated. The doors open in the escape direction.
Description
Within the use unit there are no stair requirements, and doors within the use unit are exempt from the width and swing rules. Not yet checkable: stable use and door swing are not typed in the model.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 12)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-001
Escape route to an exit or stair at most 50 m
From no point of an interior space may the route to the nearest exit to the outside or the nearest stair (vertical escape route) exceed 50 m. The 50 m apply only where two separate exits or stairs can be reached; otherwise the 35 m limit applies (VKF-16-15-002).
-
VKF-16-15-029
High-rise buildings: safety stairwells with airlocks
In high-rise buildings, storeys above ground are served by safety stairwells. These are vertical escape routes specially protected against the entry of smoke and fire (pressurized smoke control system).
-
VKF-16-15-030
Atria and inner courtyards: escape routes only with smoke and heat exhaust, verified
Escape routes across atria and inner courtyards are allowed if smoke and heat exhaust systems ensure safe walkability, shown by a verification. For further fire protection requirements for buildings with atria, the appendix refers to the VKF fire protection explanation on buildings with atria and inner courtyards.