Rule Fire protection directive 16-15 Escape and rescue routes

Escape route to an exit or stair at most 50 m

VKF-16-15-001 pragmaticBIM.ch/vkf-16-15-001

From no point of an interior space may the route to the nearest exit to the outside or the nearest stair (vertical escape route) exceed 50 m. The 50 m apply only where two separate exits or stairs can be reached; otherwise the 35 m limit applies (VKF-16-15-002).

Description

The check reads the route length computed from the geometry, from the most remote point of the space through its doors.

Source

VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)