Rule Fire protection directive 16-15 Escape and rescue routes
Escape route to an exit or stair at most 50 m
VKF-16-15-001
pragmaticBIM.ch/vkf-16-15-001
From no point of an interior space may the route to the nearest exit to the outside or the nearest stair (vertical escape route) exceed 50 m. The 50 m apply only where two separate exits or stairs can be reached; otherwise the 35 m limit applies (VKF-16-15-002).
Description
The check reads the route length computed from the geometry, from the most remote point of the space through its doors.
Source
VKF-Brandschutzrichtlinie 16-15 Flucht- und Rettungswege (2015) (p. 6)
More rules for Fire protection directive 16-15 Escape and rescue routes
-
VKF-16-15-002
Escape route with a single exit at most 35 m
Where only one exit to the outside or only one stair serves as vertical escape route, the route from the most remote point of an interior space is limited to 35 m. The model does not show whether a second, independent escape route exists, so the check reports routes above 35 m as a warning.
-
VKF-16-15-003
Doors on escape routes: clear width at least 0.90 m
A door that an escape route passes through needs a clear opening width of at least 0.90 m. Depending on the use, smaller sizes are allowed, for example for doors to ancillary or small rooms.
-
VKF-16-15-004
Doors on escape routes: clear height at least 2.00 m
Doors on escape routes need a clear passage height of 2.00 m; use-specific deviations are possible. The check reads the overall door height (IfcDoor.OverallHeight): if even that is below 2.00 m, the clear height is too small.